Power Quality Study and Diagnostics
A study to find the cause of trips, overheating or a low power factor, with full scope under IEEE 519-2022, EN 50160 and ITIC classification. We run the measurement, interpret the data and recommend mitigation: the report ends in concrete actions.
Six steps, one actionable report
Class A measurement over 7 to 10 days
We install a Fluke 1770/1775/1777 analyzer (Class A per IEC 61000-4-30) at the point of interest. Continuous measurement at 10-minute resolution over the period IEEE 519 recommends.
IEEE 519-2022 + EN 50160 assessment
Compliance analysis against Table 1 (voltage) and Table 2 (current) of IEEE 519-2022. Cross-check against EN 50160 for voltage quality. Identification of harmonic sources by spectral pattern.
K-factor and loss calculations
K-factor for transformer sizing. Estimated harmonic losses in cables (skin effect) and transformers (eddy currents).
Events on the ITIC curve
Every recorded sag/swell is classified against the ITIC (CBEMA) curve to determine whether each event fell in the no-interruption region (the equipment should keep running), the prohibited region (overvoltages that can damage it) or the no-damage region (the equipment may stop, but should not be damaged).
Complete technical report
A Word document with 20+ sections: cover, table of contents, executive summary with green/yellow/red traffic lights, harmonic tables, trend charts, glossary and prioritized recommendations.
Recommendations with Danfoss solutions
If mitigation is needed, we put concrete options on the table: AAF active filters, AHF passive filters, AFE VFDs or a combination. Each option with an estimated cost, payback and alternatives.
Three steps and typical lead times
The study is scheduled without stopping operations. Lead times are typical for one measurement point; with several points they are confirmed in the proposal.
- 01 Typical time 1 day
Short technical visit
We review the symptom (trips, overheating, power factor), the single-line diagram and the points where it makes sense to measure.
- 02 Typical time 7 days
On-site measurement
A Fluke Class A analyzer logging at 10-minute intervals for a full week, to capture operating peaks, weekends and maintenance.
- 03 Typical time 1–2 weeks
Report and recommendations
A technical report with the diagnosis, the assessment against IEEE 519-2022 and EN 50160 and the prioritized mitigation options.
If what you need is to prove compliance to the utility, see our IEEE 519 compliance audit in Panama.
If the study confirms excessive harmonics, mitigation usually means harmonic filters, active or passive.
What clients ask before we start
Short answers to the questions that usually come up in the first technical conversation. Exact lead times are confirmed in the proposal.
Q01 How is this study different from an IEEE 519 audit?
Q02 Does the plant have to stop for the measurement?
Q03 I already have a CSV file from a Fluke analyzer. Is it useful?
Q04 What is delivered at the end?
Is your plant seeing trips, overheating or a low power factor?
Before investing in filters or power factor correction, measure. A well-run study saves you money spent in the wrong place.
Request a study